Model NO.: YJV/YJV22/YJV32
Voltage Rating: 12/20kv
No.of Cores: 1-5 Cores
Applicable Standard: IEC60502 or Others
Max Working Temp: 90 Degrees
Max Shott Circuit Temp: 250 Degrees
Capacity: 2000km/Month
Delivery Length: Accord with The Request
Min.Order Qty: 1km
Trademark: Jiapu
Transport Package: Wooden Drum or Wooden&Steel Drum
Specification: IEC, ASTM, DIN, BS, GB, Any standard
Origin: Henan China
HS Code: 8544601200
Model NO.: YJV/YJV22/YJV32
Voltage Rating: 12/20kv
No.of Cores: 1-5 Cores
Applicable Standard: IEC60502 or Others
Max Working Temp: 90 Degrees
Max Shott Circuit Temp: 250 Degrees
Capacity: 2000km/Month
Delivery Length: Accord with The Request
Min.Order Qty: 1km
Trademark: Jiapu
Transport Package: Wooden Drum or Wooden&Steel Drum
Specification: IEC, ASTM, DIN, BS, GB, Any standard
Origin: Henan China
HS Code: 8544601200
12/20kV Copper Conductor XLPE Insulated armoured Power CableApplication:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Prpperty:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specification:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
 No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
6.0 |
2.5 |
0.1 |
1.2 |
0.2 |
1.9 |
37.9 |
1.87 |
2.32 |
3 X 35 |
6.9 |
2.5 |
0.1 |
1.3 |
0.5 |
2.0 |
41.5 |
2.10 |
2.73 |
3 X50 |
8.2 |
2.5 |
0.1 |
1.3 |
0.5 |
2.0 |
44.3 |
2.37 |
3.22 |
3 X 70 |
9.7 |
2.5 |
0.1 |
1.4 |
0.5 |
2.1 |
47.9 |
2.77 |
4.00 |
3 X 95 |
11.3 |
2.5 |
0.1 |
1.4 |
0.5 |
2.2 |
51.6 |
3.21 |
4.91 |
3 X 120 |
12.8 |
2.5 |
0.1 |
1.5 |
0.5 |
2.4 |
55.4 |
3.69 |
5.84 |
3 X 150 |
14.2 |
2.5 |
0.1 |
1.5 |
0.5 |
2.5 |
58.6 |
4.15 |
6.85 |
3 X 185 |
15.9 |
2.5 |
0.1 |
1.5 |
0.5 |
2.6 |
62.5 |
4.73 |
8.11 |
3 X 240 |
18.3 |
2.6 |
0.1 |
1.6 |
0.5 |
2.7 |
68.5 |
5.62 |
10.05 |
3 X 300 |
20.4 |
2.8 |
0.1 |
1.7 |
0.5 |
2.9 |
74.5 |
6.55 |
12.11 |
3 X 400 |
23.2 |
3.0 |
0.1 |
1.9 |
0.8 |
3.2 |
83.6 |
8.78 |
15.86 |
3 X 500 |
26.4 |
3.2 |
0.1 |
2.1 |
0.8 |
3.4 |
93.0 |
10.52 |
18.85 |
2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
6.0 |
3.4 |
0.1 |
1.3 |
0.5 |
2.0 |
43.4 |
2.16 |
2.61 |
3 X 35 |
6.9 |
3.4 |
0.1 |
1.3 |
0.5 |
2.0 |
45.4 |
2.36 |
2.99 |
3 X50 |
8.2 |
3.4 |
0.1 |
1.4 |
0.5 |
2.2 |
48.8 |
2.69 |
3.54 |
3 X 70 |
9.7 |
3.4 |
0.1 |
1.5 |
0.5 |
2.3 |
52.4 |
3.10 |
4.33 |
3 X 95 |
11.3 |
3.4 |
0.1 |
1.5 |
0.5 |
2.4 |
56.1 |
3.56 |
5.26 |
3 X 120 |
12.8 |
3.4 |
0.1 |
1.5 |
0.5 |
2.5 |
59.5 |
4.04 |
6.19 |
3 X 150 |
14.2 |
3.4 |
0.1 |
1.5 |
0.5 |
2.6 |
62.7 |
4.49 |
7.19 |
3 X 185 |
15.9 |
3.4 |
0.1 |
1.6 |
0.5 |
2.6 |
66.6 |
5.12 |
8.49 |
3 X 240 |
18.3 |
3.4 |
0.1 |
1.7 |
0.5 |
2.8 |
72.4 |
5.99 |
10.42 |
3 X 300 |
20.4 |
3.4 |
0.1 |
1.8 |
0.5 |
3.0 |
77.5 |
6.86 |
12.42 |
3 X 400 |
23.2 |
3.4 |
0.1 |
1.9 |
0.8 |
3.2 |
85.4 |
8.97 |
16.05 |
3 X 500 |
26.4 |
3.4 |
0.1 |
2.0 |
0.8 |
3.4 |
93.7 |
10.65 |
19.50 |
3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
6.0 |
4.5 |
0.1 |
1.4 |
0.5 |
2.1 |
48.6 |
2.53 |
2.98 |
3 X 35 |
6.9 |
4.5 |
0.1 |
1.4 |
0.5 |
2.2 |
50.7 |
2.76 |
3.39 |
3 X50 |
8.2 |
4.5 |
0.1 |
1.5 |
0.5 |
2.3 |
53.9 |
3.10 |
3.95 |
3 X 70 |
9.7 |
4.5 |
0.1 |
1.5 |
0.5 |
2.4 |
57.4 |
3.51 |
4.74 |
3 X 95 |
11.3 |
4.5 |
0.1 |
1.5 |
0.5 |
2.6 |
61.2 |
4.05 |
5.75 |
3 X 120 |
12.8 |
4.5 |
0.1 |
1.6 |
0.5 |
2.6 |
64.7 |
4.56 |
6.72 |
3 X 150 |
14.2 |
4.5 |
0.1 |
1.6 |
0.5 |
2.7 |
67.9 |
5.04 |
7.74 |
3 X 185 |
15.9 |
4.5 |
0.1 |
1.7 |
0.5 |
2.8 |
71.9 |
5.66 |
9.04 |
3 X 240 |
18.3 |
4.5 |
0.1 |
1.8 |
0.5 |
3.0 |
77.7 |
6.56 |
11.00 |
3 X 300 |
20.4 |
4.5 |
0.1 |
1.9 |
0.8 |
3.2 |
84.1 |
8.39 |
13.96 |
3 X 400 |
23.2 |
4.5 |
0.1 |
2.0 |
0.8 |
3.3 |
90.5 |
9.71 |
16.79 |
3 X 500 |
26.4 |
4.5 |
0.1 |
2.1 |
0.8 |
3.5 |
98.8 |
11.45 |
20.57 |
4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
3 X 35 |
6.9 |
5.5 |
0.1 |
1.5 |
0.5 |
2.4 |
55.6 |
3.14 |
3.77 |
3 X50 |
8.2 |
5.5 |
0.1 |
1.5 |
0.5 |
2.5 |
58.6 |
3.49 |
4.34 |
3 X 70 |
9.7 |
5.5 |
0.1 |
1.5 |
0.5 |
2.6 |
62.1 |
3.93 |
5.16 |
3 X 95 |
11.3 |
5.5 |
0.1 |
1.6 |
0.5 |
2.6 |
65.7 |
4.46 |
6.16 |
3 X 120 |
12.8 |
5.5 |
0.1 |
1.7 |
0.5 |
2.7 |
69.4 |
5.00 |
7.15 |
3 X 150 |
14.2 |
5.5 |
0.1 |
1.7 |
0.5 |
2.8 |
72.6 |
5.49 |
8.19 |
3 X 185 |
15.9 |
5.5 |
0.1 |
1.8 |
0.5 |
3.0 |
76.9 |
6.16 |
9.53 |
3 X 240 |
18.3 |
5.5 |
0.1 |
1.9 |
0.8 |
3.2 |
83.9 |
7.87 |
12.31 |
3 X 300 |
20.4 |
5.5 |
0.1 |
2.0 |
0.8 |
3.2 |
88.6 |
8.96 |
14.52 |
3 X 400 |
23.2 |
5.5 |
0.1 |
2.1 |
0.8 |
3.5 |
95.4 |
10.35 |
17.43 |
3 X 500 |
26.4 |
5.5 |
0.1 |
2.2 |
0.8 |
3.7 |
103.7 |
12.45 |
20.23 |
5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
3 X 35 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
3 X50 |
8.2 |
8.0 |
0.1 |
1.7 |
0.5 |
2.8 |
70.4 |
4.56 |
5.41 |
3 X 70 |
9.7 |
8.0 |
0.1 |
1.7 |
0.5 |
2.9 |
73.9 |
5.04 |
6.26 |
3 X 95 |
11.3 |
8.0 |
0.1 |
1.8 |
0.5 |
3.0 |
77.7 |
5.62 |
7.32 |
3 X 120 |
12.8 |
8.0 |
0.1 |
1.9 |
0.8 |
3.2 |
82.8 |
6.99 |
9.15 |
3 X 150 |
14.2 |
8.0 |
0.1 |
1.9 |
0.8 |
3.2 |
85.8 |
7.56 |
10.26 |
3 X 185 |
15.9 |
8.0 |
0.1 |
2.0 |
0.8 |
3.3 |
89.9 |
8.30 |
11.67 |
3 X 240 |
18.3 |
8.0 |
0.1 |
2.1 |
0.8 |
3.5 |
95.7 |
9.36 |
13.79 |
3 X 300 |
20.4 |
8.0 |
0.1 |
2.2 |
0.8 |
3.6 |
100.6 |
10.51 |
16.07 |
3 X 400 |
23.2 |
8.0 |
0.1 |
2.3 |
0.8 |
3.8 |
107.2 |
11.99 |
19.07 |
3 X 500 |
26.4 |
8.0 |
0.1 |
2.4 |
0.8 |
4.0 |
120.1 |
14.15 |
23.85 |
Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Prpperty:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specification:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
 No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
6.0 |
2.5 |
0.1 |
1.2 |
0.2 |
1.9 |
37.9 |
1.87 |
2.32 |
3 X 35 |
6.9 |
2.5 |
0.1 |
1.3 |
0.5 |
2.0 |
41.5 |
2.10 |
2.73 |
3 X50 |
8.2 |
2.5 |
0.1 |
1.3 |
0.5 |
2.0 |
44.3 |
2.37 |
3.22 |
3 X 70 |
9.7 |
2.5 |
0.1 |
1.4 |
0.5 |
2.1 |
47.9 |
2.77 |
4.00 |
3 X 95 |
11.3 |
2.5 |
0.1 |
1.4 |
0.5 |
2.2 |
51.6 |
3.21 |
4.91 |
3 X 120 |
12.8 |
2.5 |
0.1 |
1.5 |
0.5 |
2.4 |
55.4 |
3.69 |
5.84 |
3 X 150 |
14.2 |
2.5 |
0.1 |
1.5 |
0.5 |
2.5 |
58.6 |
4.15 |
6.85 |
3 X 185 |
15.9 |
2.5 |
0.1 |
1.5 |
0.5 |
2.6 |
62.5 |
4.73 |
8.11 |
3 X 240 |
18.3 |
2.6 |
0.1 |
1.6 |
0.5 |
2.7 |
68.5 |
5.62 |
10.05 |
3 X 300 |
20.4 |
2.8 |
0.1 |
1.7 |
0.5 |
2.9 |
74.5 |
6.55 |
12.11 |
3 X 400 |
23.2 |
3.0 |
0.1 |
1.9 |
0.8 |
3.2 |
83.6 |
8.78 |
15.86 |
3 X 500 |
26.4 |
3.2 |
0.1 |
2.1 |
0.8 |
3.4 |
93.0 |
10.52 |
18.85 |
2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
6.0 |
3.4 |
0.1 |
1.3 |
0.5 |
2.0 |
43.4 |
2.16 |
2.61 |
3 X 35 |
6.9 |
3.4 |
0.1 |
1.3 |
0.5 |
2.0 |
45.4 |
2.36 |
2.99 |
3 X50 |
8.2 |
3.4 |
0.1 |
1.4 |
0.5 |
2.2 |
48.8 |
2.69 |
3.54 |
3 X 70 |
9.7 |
3.4 |
0.1 |
1.5 |
0.5 |
2.3 |
52.4 |
3.10 |
4.33 |
3 X 95 |
11.3 |
3.4 |
0.1 |
1.5 |
0.5 |
2.4 |
56.1 |
3.56 |
5.26 |
3 X 120 |
12.8 |
3.4 |
0.1 |
1.5 |
0.5 |
2.5 |
59.5 |
4.04 |
6.19 |
3 X 150 |
14.2 |
3.4 |
0.1 |
1.5 |
0.5 |
2.6 |
62.7 |
4.49 |
7.19 |
3 X 185 |
15.9 |
3.4 |
0.1 |
1.6 |
0.5 |
2.6 |
66.6 |
5.12 |
8.49 |
3 X 240 |
18.3 |
3.4 |
0.1 |
1.7 |
0.5 |
2.8 |
72.4 |
5.99 |
10.42 |
3 X 300 |
20.4 |
3.4 |
0.1 |
1.8 |
0.5 |
3.0 |
77.5 |
6.86 |
12.42 |
3 X 400 |
23.2 |
3.4 |
0.1 |
1.9 |
0.8 |
3.2 |
85.4 |
8.97 |
16.05 |
3 X 500 |
26.4 |
3.4 |
0.1 |
2.0 |
0.8 |
3.4 |
93.7 |
10.65 |
19.50 |
3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
6.0 |
4.5 |
0.1 |
1.4 |
0.5 |
2.1 |
48.6 |
2.53 |
2.98 |
3 X 35 |
6.9 |
4.5 |
0.1 |
1.4 |
0.5 |
2.2 |
50.7 |
2.76 |
3.39 |
3 X50 |
8.2 |
4.5 |
0.1 |
1.5 |
0.5 |
2.3 |
53.9 |
3.10 |
3.95 |
3 X 70 |
9.7 |
4.5 |
0.1 |
1.5 |
0.5 |
2.4 |
57.4 |
3.51 |
4.74 |
3 X 95 |
11.3 |
4.5 |
0.1 |
1.5 |
0.5 |
2.6 |
61.2 |
4.05 |
5.75 |
3 X 120 |
12.8 |
4.5 |
0.1 |
1.6 |
0.5 |
2.6 |
64.7 |
4.56 |
6.72 |
3 X 150 |
14.2 |
4.5 |
0.1 |
1.6 |
0.5 |
2.7 |
67.9 |
5.04 |
7.74 |
3 X 185 |
15.9 |
4.5 |
0.1 |
1.7 |
0.5 |
2.8 |
71.9 |
5.66 |
9.04 |
3 X 240 |
18.3 |
4.5 |
0.1 |
1.8 |
0.5 |
3.0 |
77.7 |
6.56 |
11.00 |
3 X 300 |
20.4 |
4.5 |
0.1 |
1.9 |
0.8 |
3.2 |
84.1 |
8.39 |
13.96 |
3 X 400 |
23.2 |
4.5 |
0.1 |
2.0 |
0.8 |
3.3 |
90.5 |
9.71 |
16.79 |
3 X 500 |
26.4 |
4.5 |
0.1 |
2.1 |
0.8 |
3.5 |
98.8 |
11.45 |
20.57 |
4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
3 X 35 |
6.9 |
5.5 |
0.1 |
1.5 |
0.5 |
2.4 |
55.6 |
3.14 |
3.77 |
3 X50 |
8.2 |
5.5 |
0.1 |
1.5 |
0.5 |
2.5 |
58.6 |
3.49 |
4.34 |
3 X 70 |
9.7 |
5.5 |
0.1 |
1.5 |
0.5 |
2.6 |
62.1 |
3.93 |
5.16 |
3 X 95 |
11.3 |
5.5 |
0.1 |
1.6 |
0.5 |
2.6 |
65.7 |
4.46 |
6.16 |
3 X 120 |
12.8 |
5.5 |
0.1 |
1.7 |
0.5 |
2.7 |
69.4 |
5.00 |
7.15 |
3 X 150 |
14.2 |
5.5 |
0.1 |
1.7 |
0.5 |
2.8 |
72.6 |
5.49 |
8.19 |
3 X 185 |
15.9 |
5.5 |
0.1 |
1.8 |
0.5 |
3.0 |
76.9 |
6.16 |
9.53 |
3 X 240 |
18.3 |
5.5 |
0.1 |
1.9 |
0.8 |
3.2 |
83.9 |
7.87 |
12.31 |
3 X 300 |
20.4 |
5.5 |
0.1 |
2.0 |
0.8 |
3.2 |
88.6 |
8.96 |
14.52 |
3 X 400 |
23.2 |
5.5 |
0.1 |
2.1 |
0.8 |
3.5 |
95.4 |
10.35 |
17.43 |
3 X 500 |
26.4 |
5.5 |
0.1 |
2.2 |
0.8 |
3.7 |
103.7 |
12.45 |
20.23 |
5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor |
Nominal Diameter of Conductor |
Nominal Thickness of Insulation |
Nominal Thickness of Copper Tape Screen |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Steel Tape Armouring |
Nominal Thickness of PVC Sheath |
Approx. Overall Diameter |
Approx. Weight |
|
Al Conductor |
Cu Conductor |
||||||||
No. X mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/m |
kg/m |
3 X 25 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
3 X 35 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
3 X50 |
8.2 |
8.0 |
0.1 |
1.7 |
0.5 |
2.8 |
70.4 |
4.56 |
5.41 |
3 X 70 |
9.7 |
8.0 |
0.1 |
1.7 |
0.5 |
2.9 |
73.9 |
5.04 |
6.26 |
3 X 95 |
11.3 |
8.0 |
0.1 |
1.8 |
0.5 |
3.0 |
77.7 |
5.62 |
7.32 |
3 X 120 |
12.8 |
8.0 |
0.1 |
1.9 |
0.8 |
3.2 |
82.8 |
6.99 |
9.15 |
3 X 150 |
14.2 |
8.0 |
0.1 |
1.9 |
0.8 |
3.2 |
85.8 |
7.56 |
10.26 |
3 X 185 |
15.9 |
8.0 |
0.1 |
2.0 |
0.8 |
3.3 |
89.9 |
8.30 |
11.67 |
3 X 240 |
18.3 |
8.0 |
0.1 |
2.1 |
0.8 |
3.5 |
95.7 |
9.36 |
13.79 |
3 X 300 |
20.4 |
8.0 |
0.1 |
2.2 |
0.8 |
3.6 |
100.6 |
10.51 |
16.07 |
3 X 400 |
23.2 |
8.0 |
0.1 |
2.3 |
0.8 |
3.8 |
107.2 |
11.99 |
19.07 |
3 X 500 |
26.4 |
8.0 |
0.1 |
2.4 |
0.8 |
4.0 |
120.1 |
14.15 |
23.85 |
Oled Display Module,Segment Led Display Module,Module Pcb Oled Display,Oled Display Micro
ESEN Optoelectronics Technology Co., Ltd, , https://www.esenoptoelectronics.com